AHU-SELECTION GUIDE
Air Handling Unit (AHU) Selection Guide
https://www.systemair.com/fileadmin/user_upload/systemair-b2b/Support/Media_Center/Air_Handling_Units/AHU_SBA-BA_2018.pdf
Introduction:
Selection of AHU includes the type of AHU, filters, coils,
panels, fans, and a few other components. Any change in specification of these
items directly affects the performance, quality, capacity, and cost of the air
handling units. This document explains various terminology and standards used
in the industries at the macro level. The readers are advised to refer to the
latest standards & manufacturer data to get specified accurate information.
Click here for Air
Handling Unit (AHU) performance calculation.
Types of AHU
- Horizontal
floor mount - All major components are aligned to the base tray
and it makes maintenance-friendly.
- Vertical
floor mount – Designed to occupy less space
- Ceiling suspended – Hanged from the ceiling inside the “false ceiling” and zero floor space
- Draw Thorough type: Blower after the filter, coils and all
- Blow through type: Blower before all.
A typical AHU consists of the below components in place
Filters
European Standards EN 779& EN 1822
These standards are describing the classification &
characteristic requirement of filters used in building ventilation &
industrial process.
Based on the particulate size it classifies the filters as
below
- Classes
G1, G2, G3 & G4 – Defining the requirement of coarse dust particulate
size > 10µ
- Classes
M5, M6, F7, F8 & F9 - Defining the requirement of fine dust
particulate size 1µ - 10µ
- Classes
E10, E11, E12, H13, H14, U15 & U16 – Defining the requirement of
suspended particulate sizes <1µ
Based on the type of filtration the filters are grouped
together as below
- Coarse
filter requirements are defined under classes G1-G4 of E 779
- Medium
filter requirements are defined under classes M5-M6 of E 779
- Fine
filter requirements are defined under classes F7-F9 of EN 779
- High-efficiency
filter requirements are defined under classes E10-U16 of EN 1822
ISO 29463
It is derived from EN1822 and both are based on MPPS – Most
Penetrating Particulate Size. MPPS is the particulate size at which an air
filter gives minimum arrestance. But they have some differences in leakage test
methods. Both standards are describing the requirement for high efficiency EPA,
HEPA & ULPA filters.
ISO 16890
It replaces EN 779 from the year 2018. The EN 779 classifies
the filters based on the filtration efficiency of particulate matter size of
0.4µ. Whereas ISO 16890 classifies the filters based on a spectrum of particulate
sizes from 0.3µ to 10µ. It has three major classifications used by WHO (World
health organization) as below
PM1 – Particulate sizes less than 1µ
PM2.5 – Particulate sizes less than 2.5µ
PM10 – Particulate sizes less than 10µ
The particulate matter >10µ are not breathed, the
particulate matter <10µ can penetrate bronchi, the particulate matter
<2.5 µ can penetrate pulmonary alveoli and the particulate matter <1 µ
can penetrate alveoli capillary barriers.
European standard EN 15805
It describes the header framing dimensions of filter used in
air intake systems and air handling units.
MERV–Minimum Efficiency reporting value
It is described in ASHRAE 52.2 to report the effectiveness
of filters. It classifies the filters from MERV1 to MERV16. Higher the rating
filters will allow fewer dust particles. This standard is intended to assist
the end-user and specifier in their selection of appropriate filters for
various applications.
Coil
All standard values in this document are referring to water
as tube side fluid. Please refer AHRI 410 & ASHRAE standard for other
fluids.
Chilled water details:
As per AHRI 410: 2001 the acceptable range of values are
- Chilled
water inlet temperature 35° F ~ 65ׄ° F
- Water
velocity - 1 fps ~ 8 fps
- Minimum
fin surface temperature >32° F
- Minimum
tube surface temperature >32° F
Typical values are
- Chilled
water in & out temperature 45° F & 55° F
- Estimated
Δt - 10° F
- Chilled
water pressure drops - max. 20 ft H2O
- Flow
rate - 2.4 gpm/ton
- Water
velocity – 2fps~3fps
An increase in flow rate causes the velocity & pressure
drop to increase. Then the water stays very little time inside the coil, which
causes the air leaving temperature to grow and gives a reduced air Δt. To
achieve the required air temperature and coil performance we may have to
increase the number of fins/ft, which results in a price increase for the coil.
The maximum pressure drop across the coil falls between 20 ~
24 ft H2O. But it is advisable to keep as low as possible and typical values
fall less than 10 ft H2O. The pressure drop in the coil is controlled by the
number of tubes in the coil.
The size, length & width of a coil is decided based on
the fin length, design air face velocity, and required tonnage of the coil.
Fins
Aluminum is the standard material for fins used in most
applications. Copper fins are recommended for corrosive environments. The
number of fins various between 8 fins/inch to 14 fins/inch based on the heat
transfer requirement.
When there is an increase in water flow rate the heat
transfer rate reduces across the coil due to higher velocity, which requires
fewer fins/inch. The required number of fins/inch will be close to 8. There
will be a decrease in price for the coil, but we will end up with higher
velocity & pressure drop.
Typical aluminium fin thickness falls between 0.006” ~
0.0095”.
Tubes
With ½” tube OD, the performance will be increased slightly,
and not a major difference between 5/8” tube OD. Like tube OD with an increase
in tube thickness, there will not be a big difference in performance, only the
coil life can be improved. The typical thickness for coils is 0.025” ~ 0.035”.
Number of rows in coil
A typical number of rows of a coil for AHU is 4. An increase
in the number of rows results in more Δt, low discharge air temperature, more
moisture removal& higher dehumidification & more air pressure drops for
the fan.
Typically, an increased number of rows will be used where
the intake to an AHU is 100% fresh air, like operation theatres.
Drain pan
A drain pan for individual coil section is expected, because
the condensation in the upper coil may block the airflow in the lower one. And
the main drain pan is required at the bottom of the full coil, which drains out
the water.
Reynold’s number of an AHU coil is dependent on the tube
inner diameter, fluid velocity & tube type. Reynold’s number can be
controlled based on the circuit & adding a turbulator. Adding a turbulator
may result in a higher pressure drop.
Refer latest AHRI 410 for the method of calculating Reynolds
number and acceptable values.
Fouling
Fouling is the formation of sediments and any other matters
that form inside the tube over a period. Fouling increases pressure drop
reduces heat transfer, and obstruct fluid flow.
There is no straight method to calculate the fouling and it
is the value directly added to thermal resistance for design &
manufacturing of coil. This defines the duration for cleaning frequency.
The unit of fouling is ft²-°F-ht/Btu. Value zero will be
considered for fouling when possible and the typical value will be 0.0005 for
internal & 0.001 for external.
Air side details
As per AHRI 410: 2001 the acceptable range of values are
- Air
face velocity – 200 fpm ~ 800 fpm
- Entering
air dry-bulb temperature – 65° F ~ 100° F
- Entering
air wet-bulb temperature – 60° F ~ 85° F
Typical values are
- Air
face velocity – 500 fpm
- Entering
air dry-bulb temperature –65° F ~ 80° F
- Entering
air wet-bulb temperature – 60° F ~ 70° F
- Estimated
Δt - 20° F ~ 25° F
When the air face velocity is too low heat transfer will not
take place due to lack of turbulance. At the same time when the air face
velocity is too high, the heat transfer will be very less with a higher air
pressure drop. Also, moisture carry-over will happen at high velocity which
results in water droplets all over the AHU. The air pressure drop will be very
minimal at 400 fpm of face velocity, but there will be a slight increase in the
cost of the AHU.
With the increased number of coil rows and fins, we get a
higher air pressure drop.
As a rule of thumb 400 cfm is considered for 1TR capacity in
a typical AHU. Refer to performance calculation for more details.
ASHRAE standard 33 – defines the equations for calculating
air side pressure drop, sensible cooling, dehumidification, and test
requirements.
AHU Panels
Outer skin & inner skin are usually made of galvanized
steel. Aluminum and stainless steel materials are considered as alternate for
specific requirements.
The insulation is selected based on the required thermal
resistance & sound attenuation.
Single skin AHU
- Mainly
for ventilation
- Outer
casing shall be of – 0.5mm thick; with powder coated.
- Insulation
of 25mm thick fibre glass or 15mm foam
- Suitable
for lesser flow up to 2200 cfm
Double skin AHU
- Mainly
for air conditioning
- Inner
Skin – 0.4~0.7mm thick; galvanized steel
- Outer
Skin – 0.4~0.9mm thick; with powder coated
- Insulation
of 50mm thick fibre glass or 25mm foam; insulation is sandwiched between
inner skin and outer skin.
Fans
|
Forward curved fans |
Backward curved fans |
|
Forward curved fans will have many small blades curved in
the direction of rotation. |
Backward curved fans will have less quantity of longer
blades curved opposite to the direction of rotation. |
|
Flow is tangent to the rotation |
Flow is in radial direction |
|
Requires a scroll house to convert the kinetic energy into
static energy |
No housing is required |
|
Smaller in size for a given air flow |
Larger in size for a given air flow |
|
Single inlet is suitable for high pressure low volume
Double inlet is suitable for high volume, low pressure system |
Suitable for higher efficiency & high pressure |
|
Can run with AC motor |
Requires an EC motor |
Typically, forward curved fans are used in AHUs due to the
operational requirement, cost & size.
Operating above or below the optimum design criteria can
cause noise and reduce the efficiency of the system for both forward &
backward curved fans.
Internal static pressure (ISP) = Total pressure drop caused
by all components within the system, like., filters, coils, mixing box and
other components.
External static pressure (ESP) = It is the pressure
developed in supply/return system / ducting, like., duct pressure loss, volume
control dampers, diffusers, and other components.
Total static pressure (TSP) = ESP + ISP
Each component (filters, dampers, diffusers, grills, ducts,
etc) in the given system produces some static pressure to the fan. The static
pressure to the fan is directly proportional to the flow and at the same time,
the fan cannot be operated above or below the optimum levels.
Additional information
Additional details to be considered in selecting an AHU are
given below and we are not covering in this article.
- Drip
eliminator,
- Anti-corrosive
coating to the coil
- Variable
frequency drives for fans
- Humidifiers
- De-humidification
- Belt
drive / Direct dive for the fans
- Selection
of pulley and belts
- Volume
control dampers
OUTER SKIN : 0.6 MM thick pre coated GSS INNER SKIN: 0.6 MM thick
PAluzinc sheet
FRAMEWORK : Extruded aluminum Section with/without thermal
break profile DRAIN PAN: 18 G Stainless steel(Single Skin) with 13mm nitrile
insultion INSULATION:Polyurethane foam
PANEL THICKNESS:50 MM
FAN: NICOTRA make DIDW Backward curved centrifugal blower
CONFIGURATION OF
HORIZONTAL FLOOR MOUNTED AIR HANDLING UNITS:
Mixing box section with manually operated(FA&RA) AL
dampers.
Filter section with 50 mm thick EU-4 filters and 300mm thick
EU-7 filter on common GI filter frame Cooling coil section with 6 row deep
(12.7mm OD copper tube) CHW cooling coils.
Fan section with NICOTRA make DIDW Backward curved
centrifugal Fans with drive packages and with drive motors.
NOTES:
1.
The face velocity across all types of filters
& coils has been considered as 500 FPM
2.
The cooling coils will be made of 27 G copper
tubes(12.7mm OD) having aluminum fins with MS header and GSS casing.
3.
We have included for std EEF-1 motor in all the units.
4.
PO to be released on Systemair India Pvt Ltd,
Plot No. 03, Sector 31, Ecotech-1, Kasna, Greater Noida - UP - 201308'
EXCLUSIONS:
3-way mixing valves, modulating motors, thermostat, pressure
gauges, guide vanes, thermometer gauges, DP nozzles, all types of grills, PG
device, speed regulator switch, ASP, other controls and instrumentations,
ducting, electrical cabling, louvers, valves, strainers, testing, commissioning,
installation and other accessories

Comments
Post a Comment